Grounding Cable
A+ Safety offers grounding cable from size 2 through 4/0 in yellow, black or clear. Cables ae made with extra flexible strands of soft drawn # 30 AWG (.01") copper.
Yellow: thermoplastic elastomer jacketed cable is the standard for grounding sdervive. It provides a combination of economy, felxibility and durability. The service temperature ranges from 200o to -50oF per ASTM F 855, Type 1.
Black: thermoplastic elastomer jacketed cable has a smaller diameter and thinner jacket material giving it better flexibility than the yellow cable. The service temperature ranges from 250o to -50oF per ASTM F 855, Type 1.
Clear: flexible thermoplastic (PVC or silicone) jacketed cable allows easy inspection for strand breakage. The flexibility decreases with low termper- atures. The minimum recommended service temperature is 0oF per ASTM, Type III requirements
Yellow grounding cable
|
Codes
|
|
Size 2 - 665W: *Strand diameter .35" (8.9mm) *Jacket .5" (12.7mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 14,500. 30 cycles: 10,000 *Continuous current amps, RMS, 60Hz: 200 |
SAL 2136 |
|
|
|
|
Size 1/0 - 1064W: *Strand diameter .45" (11.4mm) *Jacket .62" (15.7mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 21,000. 30 cycles: 15,000 *Continuous current amps, RMS, 60Hz: 250 |
SAL 2137 |
|
|
|
|
Size 2/0 - 1330W: *Strand diameter .49" (12.4mm) *Jacket .65" (16.5mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 27,000. 30 cycles: 20,000 *Continuous current amps, RMS, 60Hz: 300 |
SAL 2138 |
|
|
|
|
Size 4/0 - 2109W: *Strand diameter .62" (1.7mm) *Jacket .83" (21.1m) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 43,000. 30 cycles: 30,000 *Continuous current amps, RMS, 60Hz: 400 |
SAL 2139 |
|
|
|
|
Black grounding cable
|
Codes
|
|
Size 2 - 665W: *Strand diameter .35" (8.9mm) *Jacket .47" (12mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 14,500. 30 cycles: 10,000 *Continuous current amps, RMS, 60Hz: 200 |
SAL 2636 |
|
|
|
|
Size 1/0 - 1064W: *Strand diameter .45" (11.4mm) *Jacket .58" (14.7mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 21,000. 30 cycles: 15,000 *Continuous current amps, RMS, 60Hz: 250 |
SAL 2637 |
|
|
|
|
Size 2/0 - 1330W: *Strand diameter .49" (12.4mm) *Jacket .63" (16mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 27,000. 30 cycles: 20,000 *Continuous current amps, RMS, 60Hz: 300 |
SAL 2638 |
|
|
|
|
Size 3/0 - 1672W: *Strand diameter .55" (14mm) *Jacket .72" (18.3mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 36,000. 30 cycles: 25,000 *Continuous current amps, RMS, 60Hz: 350 |
SAL 2649 |
|
|
|
|
Size 4/0 - 2109W: *Strand diameter .62" (1.7mm) *Jacket .78" (19.8m) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 43,000. 30 cycles: 30,000 *Continuous current amps, RMS, 60Hz: 400 |
SAL 2639 |
|
|
|
|
Clear grounding cable
|
Codes
|
|
Size 2 - 665W: *Strand diameter .35" (8.9mm) *Jacket .53" (13.5mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 14,500. 30 cycles: 10,000 *Continuous current amps, RMS, 60Hz: 200 |
SAL 2128 |
|
|
|
|
Size 1/0 - 1064W: *Strand diameter .45" (11.4mm) *Jacket .64" (16.3mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 21,000. 30 cycles: 15,000 *Continuous current amps, RMS, 60Hz: 250 |
SAL 2137 |
|
|
|
|
Size 2/0 - 1330W: *Strand diameter .49" (12.4mm) *Jacket .7" (17.8mm) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 27,000. 30 cycles: 20,000 *Continuous current amps, RMS, 60Hz: 300 |
SAL 2133 |
|
|
|
|
Size 4/0 - 2109W: *Strand diameter .62" (1.7mm) *Jacket .84" (21.3m) *Short circuit withstand amps, RMS, 60Hz: 15 cycles: 43,000. 30 cycles: 30,000 *Continuous current amps, RMS, 60Hz: 400 |
SAL 2288 |
|
|
|
|
|
|
|
|